EWB

General Features

  • Modular design
  • Corrosion free
  • Industrial applications
  • Easy maintenance
  • Big capacity (500 – 10.000 m3/h)

Documentation

Assembling and Operation Manual

Product Catalogue

Sound Levels

Nozzel Pressure Drop

More Cooling Towers

Configuration


Model* Dissip. (kW)Dry Weight (kg)Service Weight (kg)Fan Power (kW)Length (mm)Width (mm)Height (mm)Dim. Drawing - Concrete RaftDim. Drawing - Polyester BalsaTechnical Features
* Heat rejection at the following conditions: Tin: 35,0 ºC, Tout: 30,0 ºC, Twb: 24,0 ºC
EWB 173027663500490022.0370049024807Open open icon, Download download-iconOpenopen icon, Download download-icon[-]
EWB 230036774700660022.0490049024807Openopen icon, Download download-iconOpenopen icon, Downloaddownload-icon[-]
EWB 287545976800920030.0490061025106Open open icon, Download download-iconOpenopen icon, Download download-icon[-]
EWB 3600575685151152037.0610061025106Openopen icon, Download download-iconOpenopen icon, Download download-icon[-]
EWB 34605332680086002 x 22.0735049024807Open open icon, Download download-iconOpenopen icon, Downloaddownload-icon[-]
EWB 460073558800213002 x 22.0975049024796Openopen icon, Download download-iconOpenopen icon, Download download-icon[-]
EWB 5750919311600164002 x 30.0975061025106Open open icon, Download download-iconOpenopen icon, Download download-icon[-]
EWB 72001151214525205352 x 37.01215061025106Open open icon, Download download-iconOpenopen icon, Download download-icon[-]

Additional EWB Equipment

  1. Sound Attenuator.
  2. Access ladder & Hand rail to the fan motor.
  3. Vibration Switch.
  4. Variable speed drives
  5. Basin in FGRP

Working Principles

Evaporative cooling towers are the most energy efficient means of cooling water. Hot process water or condenser water from a chiller enters the distribution system at the top of the cooling tower and falls by gravity in counter-flow to the air being drawn or forced through the cooling tower by the fan. As the air passes the water a small proportion is evaporated cooling the remaining water which is collected in the cooling tower sump. The cooled water is then returned to the process or chiller
The difference between the required cold water temperature and the wet bulb temperature (called the approach temperature), is significant in determining the size of the tower. The smaller the approach the larger the required heat exchange surface. The approach temperature must be at least 3-4 °C
. The heat exchange surface known as packing provides close contact between the air and water in open towers. High efficiency film packings provide a large surface area over which the cooling water is spread increasing the evaporative cooling effect. Splash packings can be selected for applications where the water quality is poor.